Free Engineering Tool

Valve CV Flow Coefficient Calculator

ISA-75.01 compliant sizing for liquids, gases & steam. Calculate required CV, check for choked flow & cavitation, and download a professional PDF report.

✔ Liquids, Gases & Steam✔ Choked Flow Detection✔ Cavitation Warning✔ Valve Flow Curves✔ PDF Report✔ US & Metric Units
Mode:
Units:
Fluid Properties
Relative to water at 60°F
For cavitation check
For flashing check
Gas Properties
Must be above saturation temp at P1
Valve Configuration

Enter your process conditions and click Calculate CV to see results

Required CV
Flow Coefficient (gpm/√psi)
Kv (m3/h)
Rec. CV (+25%)
ΔP (psi)

📄 Download Your Sizing Report

Fill in the valve details below to generate a professional PDF sizing report.

By submitting, you agree to receive emails from ValveMan. You can unsubscribe at any time.

* By downloading you agree to receive occasional emails from ValveMan. Unsubscribe anytime.

Valve Flow Characteristic Curve
CV vs. % Travel — enter rated CV to see your operating point

What is Valve CV (Flow Coefficient)?

The flow coefficient CV is the most important parameter for sizing a control valve. Defined by ISA-75.01, CV represents the flow rate in US gallons per minute (GPM) of 60°F water that passes through a fully open valve with a 1 psi pressure drop across it.

In metric systems the equivalent is Kv (m³/h per bar½). The relationship is: CV = 1.156 × Kv.

Liquid CV Formula (ISA-75.01)

CV = Q / √(ΔP / SG)
Q = GPM, ΔP = pressure drop (psi), SG = specific gravity

Choked ΔP = Fl² × (P1 − Ff × Pv)
Fl = pressure recovery factor, Ff = liquid critical pressure ratio factor

Gas & Vapor CV Formula (ISA-75.01)

CV = Q / (1360 × P1 × Y × √(x / (Gg × T1)))
Q = SCFH, P1 = psia, T1 = °R, Gg = sp. gravity vs air

Y = 1 − x/(3 × Fk × xT)   [choked when x ≥ Fk × xT]

Steam CV Formula

CV = W / (63.5 × Y × √(x × ρ1 × P1))
W = lb/hr, ρ1 = inlet density (lb/ft³), P1 = psia

Low Flow, Standard & High Flow Applications

For low flow (small CV, high viscosity), laminar conditions may exist (Re < 10,000) requiring a viscosity correction factor FR — this calculator flags when that applies. High flow / choked flow is automatically detected using the valve's Fl factor. Rotary valves (ball, butterfly) have lower Fl (0.55–0.70) vs. globe valves (0.85–0.95).

Frequently Asked Questions

What safety factor should I apply to CV?

Size the valve to operate 20–80% open at design flow — typically select a valve with a rated CV of 125–150% of the calculated required CV.

What does "choked flow" mean?

Choked flow occurs when ΔP exceeds a maximum limit (set by Fl). Further pressure drop increases do not increase flow. For liquids, this also risks cavitation damage.

What is cavitation?

Local pressure drops below vapor pressure, forming vapor bubbles that collapse violently — causing noise, vibration, and rapid valve damage. Use anti-cavitation trim or reduce ΔP.

Linear vs. equal percentage trim?

Linear: flow proportional to travel — ideal for constant ΔP. Equal %: equal % flow change per % travel — best for varying ΔP, better controllability across wide range.

What is the Fl pressure recovery factor?

Fl represents how much pressure recovers downstream of the vena contracta. Globe valves: high Fl ≈ 0.90. Ball/butterfly: lower Fl ≈ 0.55–0.70.