Watson McDaniel Authorized Distributor

3" Watson McDaniel 403-19-F300-1409-R Piston-Actuated Pressure Regulating (For Steam & Gas), Ductile Iron Body, Double Spring, 30 - 125 PSIG Remote Sensing, Pilot-Operated, 300# Flange

SKU: 403-19-F300-1409-R
Made in the United States
$6,533.99
Available to Order
Available Sizes
Sizes1/2" - 4"
Max Inlet Pressure450 PSIG
Body MaterialDuctile Iron
ConnectionsNPT, 150# FLG, 300# FLG
Typically ships in 3–5 business days from the manufacturer
Need it fast? Call 888-825-8800 — we may be able to expedite your order.
Estimated ship date: calculating...
Buying for a facility?

Custom quote, volume pricing, or Net 30 terms available.

Request a Formal Quote or call 888-825-8800
Sourced from Vetted Suppliers Every product is quality-checked from certified manufacturers
Need It Fast? Call 888-825-8800
Made-to-order — final sale, see return policy
Expert Support: 888-825-8800

Technical Specifications

General

Model403 Series
ServiceSteam & Air
Sizes1/2" - 4"
Part Number403-19-F300-1409-R
BrandWatson McDaniel
Manufacturer Part #403-19-F300-1409-R
Size3"
Country of OriginMade in the United States

Materials & Construction

Body MaterialDuctile Iron
Seat & DiscHardened 420 Stainless Steel (55 Rc)

Performance

Max Inlet Pressure450 PSIG
Min Inlet Pressure20 PSIG
Max Differential Pressure250 PSI
Min Differential Pressure15% of Inlet Pressure (10 PSI min)

Connections

ConnectionsNPT, 150# FLG, 300# FLG

Overview

Watson McDaniel 403-19-F300-1409-R Piston-Actuated Pressure Regulating Valve, Double Spring, 30 - 125 PSIG Remote Sensing (3" 300# Flange)

Features:

  • Pilot-operated regulators minimize outlet pressure fluctuations even when load varies.
  • Internal Sensing option (If requested, the regulator can be modified to internally sense pressure, eliminating the need for an external sensing line).
  • Ductile Iron body to handle increased pressure and temperature.
  • Hardened stainless steel seat and disc (55 RC).

Options & Features (See Specification Sheet For Full List):

403 Piston-Actuated Pilot-Operated (For Steam & Gas)

The 403 Piston-Actuated Pressure Regulating are pilot-operated, piston-actuated, pressure regulators primarily used for reducing pressure in STEAM systems. These regulators can be equipped with an optional internal sensing line which simplifies installation (Suffix I). The 403 Series has all stainless steel internals for high-pressure applications up to 450 PSIG. Double Spring Option is available for wider range of reduced pressures.

Steam: The 403 Series pilot-operated (Piston-Actuated) pressure regulating valves are used for pressure reduction on steam mains and other process equipment. Piston-actuated regulators are more compact than Diaphragm-actuated regulators. The 403 Series has a Ductile Iron body but contains all stainless steel internals for high-pressure applications up to 450 PSIG.

Gas/Air: The 403 Series pilot-operated (Piston-Actuated) pressure regulating valves are used for pressure reduction on steam mains and other process equipment. Piston-actuated regulators are more compact than Diaphragm-actuated regulators. The 403 Series has a Ductile Iron body but contains all stainless steel internals for high-pressure applications up to 450 PSIG.

The 403 Series Pilot-Operated (Piston-Actuated) pressure regulating valves are used for pressure reduction on steam mains and other process equipment. Pilot-operated regulators will maintain a constant and accurate downstream pressure regardless of fluctuations in supply pressure or usage. These regulators can be supplied with an optional internal sensing line which simplifies installation. Piston-actuated regulators are more compact than Diaphragm-actuated regulators. The 403 Series contains all stainless steel internals for high-pressure applications up to 450 PSIG. The Double-Spring option is available for a wider range of reduced pressures

Selection / Sizing / Capacities

From the Capacity chart, find the inlet pressure and required regulator outlet pressure. Follow across chart to nearest capacity (Steam, Air) that meets or slightly exceeds demand requirements. Follow vertically up to determine appropriate size. When exact application values are not shown, interpolate between values. From the spring range chart, select the spring range that accommodates the required outlet set pressure. Specify Internal or External (Remote) Pressure sensing.

Example:

  • Application: 12,500 lbs/hr of 300 PSIG Steam reduced to 125 PSIG
  • Model Code: 403-17-N-0010-R (2" 403 Series Valve, 100-200 PSIG spring range, with external sensing.