General
| Signal/Output Ratio | 1:1 |
|---|---|
| Deadband | less than 0.2 psig (0.01 bar) |
| Mounting Options | In line, mounting bracket |
| Part Number | 429-841-434 |
| Options | Low-Temperature Operation, ATEX 2014/34/EU |
| Brand | ControlAir |
| Manufacturer Part # | 429-841-434 |
| Size | 1/4" |
| Country of Origin | Made in the United States |
Materials & Construction
| Body Materials | 316 Stainless Steel |
|---|---|
| Other Materials | Stainless Steel, Nitrile, Silicone |
Performance
| Flow Capacity | 250 scfm (7,075 Nl.min) |
|---|---|
| Supply Pressure Sensitivity | 0.1 psig (0.007 bar) for a 25 psi (1.7 bar) change in suppy pressure |
| Max. Supply Pressure | 250 psig (17 bar) |
| Max. Output Pressure | 150 psig (10 bar) |
| Max. Signal Pressure | 150 psig (10 bar) |
| Ambient Temperature Limits | -40° to 200°F (-40° to 93°C) |
Connections
| Port Size | 1/2" NPT, 1/4" NPT, 3/4" NPT |
|---|---|
| Signal Port Size | 1/4" NPT |
| Exhaust Port Size (optional) | 1/2" NPT |
| Gauge Port Size | 1/4" NPT |
| Maximum Flow/Exhaust Coefficient (Cv) 1/4" port | 2.0 / 3.0 |
| Maximum Flow/Exhaust Coefficient (Cv) 1/2" port | 4.5 / 4.0 |
| Maximum Flow/Exhaust Coefficient (Cv) 3/4" port | 5 / 4.0 |
| Exhaust Capacity (3/4" port) | 80 scfm (2, 264 Nl/min) |
Dimensions & Weight
| Weight | 5.7 lbs (2.60 kg) |
|---|
Overview
ControlAir Type 6200 Series Stainless Steel High Flow Capacity Volume Booster (6200-BSLX)
Features:
- 1/4”, 1/2” or 3/4" NPT Porting
- Aluminum or 316 Stainless Steel Construction
- Integral Adjustable Bypass Valve: Allows small incremental signal changes without opening the primary valve.
- High Flow Capacity: For rapid actuator stroking.
- Soft Valve Seat Design Provides tight shutoff and eliminates leakage in steady state operation.
- High Temperature Operation: Up to 200°F (93°C), Optional 284°F (140°C)
- High Output Exhaust Vents: (2) 1/4" NPT tapped exhaust (Type 6100 option) 1/2" NPT tapped exhaust (Type 6200 standard)
- (2) 1/4" NPT Gauge Ports
- Optional Negative Bias: 4 psi (0.3 bar) negative bias of signal pressure to 'zero' I/P's
- IEC 61508 SIL3 Certified
Options & Features (See Specification Sheet For Full List):
Rapid Stroke Capability In A 316 Stainless Steel Housing
The Type 6200 Stainless Steel Volume Booster is a 1:1 signal to output relay that significantly increase the stroking speed in valve actuation system applications that require high forward airflow and exhaust capacities. Constructed of 316 stainless steel to ensure the best resistance to corrosive environments. The Type 6200 is suitable for either diaphragm or piston actuators. A fixed deadband and adjustable bypass valve combine to allow small incremental downstream adjustment without opening the main booster valve. The bypass valve is used to adjust dynamic response to provide stable operation over a wide range of actuator sizes. Negative Bias adjustment (up to -4 psi) is available to “zero” downstream pressures when using standard signal pressure ranges.